A continuous load is one that is on for more than_____ hours so conductors must be sized at____% of that load
Front
3, 125
Back
In a panelboard, the busses supplying the citcuit breakers are so arranged so that connections directly across from each other are on the same phase and the adjacent connections on each side are on different phases
true or false
Front
false
Back
An_____ transfer switch is used to switch a load from its normal primary source to the emergency source without any human interaction and a ______ transfer switch will switch a load but requires a person to operate it
Front
automatic , manual
Back
The NEC requires a minimum of ______ inches of conductor in a box and at least______ inches shall extend past the front of the box
Front
6 , 3
Back
An individual appliance branch circuit shall have a rating less than the appliances "marked rating"
True or False
Front
false
Back
Standard light fixture boxes are rated to support fixtures not weighing over_____ pounds
Front
50
Back
Four #4 awg, type THW copper current carrying conductors are installed in a conduit in a boiler connected to these conductors is _____ amps
Front
51
Back
What are the four types of fuel in generators?
Front
propane gas, natural gas, gasoline, diesel
Back
AC systems exceeding____ volts to ground that supplies premise wiring shall be grounded if on 3 phase, 4 wire wye connected circuit
Front
50
Back
A receptacle is required in any habitable room on any wall space_____inches or greater in width and with-in____ feet of a doorway or opening. Wall receptacle are to be placed no more than____feet apart
Front
24, 6, 12
Back
The maximum setting of ground fault protection shall be 1200 amperes and the maximum time delay shall be one second for ground faults equal to or greater than 300 amperes
true or false
Front
false
Back
All appliances are required to have a nameplate that indicates.....
Front
identifying name , frequency, volts/amps, watts
Back
Besides the General lighting branch circuits, name the other 20 amps circuits required by the code in a dwelling with a garage. Qty-2: ________, _________, _________, __________
Front
small appliance, laundry branch circuit, bathroom branch circuit, garage
Back
How many 10 stranded conductors are allowed in a
3 X 2 X 2 3/4 device box?
Front
5
Back
The manufactures factory testing of the ground fault equipment is considered adequate
true or false
Front
false
Back
In a location where there us heating or air conditioning equipment , a receptacle is to be installed with-in_____feet of the equipment on the same _____
Front
25, level
Back
A box, with clamps, contains 2 # 14/2 NM cables and a receptacle. How much volume must you allow for: clamps______ cu. in, Grounds________, cu. in & receptacle______cu. in
Front
2, 2, 4
Back
What is the minimum cubic-inch volume required for a box that will contain one internal clamp, one switch ( supplied by #14 conductors), and one receptacle ( supplied by # 12 conductors ), two 14/2 NM cables?
Front
30 cu. in
Back
For circuit rated at less than 100 amperes, the terminals for the conductor(s) terminations are rated for ______ degree C conductors
Front
60
Back
A 3200 square foot house, with 600 sq. ft. of additional non-adaptable unfinshed space, requires how many 15 amps lighting branch circuits?
Front
6
Back
How many number 14 conductors allowed in a 4" square box that is 1 1/4 deep?
Front
5
Back
Storage batteries used in emergency systems shall be capable of maintaining the load for____ hours (minimum) and without the voltage dropping below____percent of normal
Front
1 1/2 , 87 1/2
Back
How much volume must you allow in a box for a number 12 conductor?
Front
2.25 cu. in
Back
In bathroom a receptacle must be installed on an______ wall with-in____Ft of the edge of the_____ or in cabinet no more than____inches below the counter top
Front
adjacent, 3, basin , 12
Back
A panelboard's maximum rating is determined by the current carrying capacity of the panel boards internal main______
Front
buss bars
Back
Eight conductors in a conduit must be de-rated to____%
Front
70
Back
If a load is expected to be on for more than three hours, then it is considered to be a (an)________ load
Front
continuous
Back
When the ampacity of a conductor does not correspond to the standard fuse or circuit breaker rating, the code allows you use the next higher rating unless that rating is excess of______ amps
Front
800
Back
Halls greater than_____ feet in length, as measured down the_____ are required to have receptacle
Front
10, center line
Back
A switchboard can be accessible from the front and rear
true or false
Front
true
Back
Split-wired duplex receptacles, where only one 1/2 of it is switched, do meet the spacing requirements required by the NEC
true or false
Front
true
Back
The NEC requires receptacles to be mounted with the ground up
true or false
Front
false
Back
A_____ _______ is the circuit conductors between the final over current protection device and the outlets
Front
branch circuit
Back
If an appliance rating does not exceed 1/8 horsepower or does not exceed 300 volt amps, the branch circuit over current device may serve as the appliances disconnecting means
True or False
Front
true
Back
A service is supplied by three number 500 KC MIL conductors per phase, What is the minimum size grounding electrode conductor required?
Front
3/0
Back
Foyers, not part of hall, that have an area greater than_____sq.ft shall have a receptacle installed on any wall space greater than_____feet in width
Front
60, 3
Back
The conductor on the "high-leg" of a 3 phase open delta system must be marked or identified by using the color_____and in panel installed on the _____ phase
Front
orange, B
Back
What table is used to find the value of volt-amperes per square foot for general lighting loads?
Front
220.12
Back
Ground fault protection for equipment shall be provided for solidly grounded wye electrical servies of more than how many volts to ground?
Front
150 volts
Back
In walls constructed of noncombustible materials you are allowed to have a box set back in the wall no more than_____of an inch and gaps around the box cannot exceed_____ of an inch
Front
1/4, 1/8
Back
When sections of electrical equipment are bolted together, non conductive paint, enamel, or similar coatings must be removed to insure good _____ ______
Front
electrical continuity
Back
The NEC allows grounding conductors to be spliced with _________ welding processes
Front
exothermic
Back
Rod and pipe electrodes shall not be less than____feet in length
Front
8
Back
Construction plans for a building are usually called _________ or working drawings and the documents governing all of the material to be used and work to be performed on a construction project are called the ______
Front
blue prints, specifications
Back
Conductors installed in a conduit, that is less than 24 inches long, are not required to be de-rated
True or False
Front
true
Back
Show window lighting is required to be calculated at____va per linear foot and in commercial buildings, receptacles outlets are to be calculated at________va each
Front
200, 180
Back
In resistance, the minimum number of lighting branch circuits required is based on ______VA per square ft
Front
3
Back
That portion of the wiring system between the final over current device protecting the circuit and the outlet(s) is called a _________ circuit
Front
branch
Back
The oil in a liquid filled transformer is for cooling and insulation
true or false
Front
true
Back
To regard to a commonly used emergency, back-up power source, the initials U P S stand for________ power supply and it's most commonly used source of short term power is ______
Front
uninterruptible, batteries
Back
Section 2
(29 cards)
At least one switched-controlled lighting outlet must be installed in a space containing a water heater
true or false
Front
true
Back
On a kitchen island, a receptacle must be installed to serve ant space greater than______" by______"
Front
24 , 12
Back
A lighting fixture must be installed every exterior entrance with ______ ____ access
Front
grade level
Back
On a balcony, a receptacle must be installed no more than____feet above the walking surface
Front
6 1/2
Back
The NEC requires receptacles to be mounted outside of a house in the ______ and _____ of the house, be _____ accessible and not be located higher than____feet above grade level
Front
front, back, readily, 6 1/2
Back
A detached garage that has no wiring is not required to have a receptacle
true or false
Front
true
Back
The type NM cable must be secured with-in____" of a box without a clamp, with-in____" of a box with a clamp and every_____feet thereafter
Front
8, 12, 4 1/2
Back
In unfinished basements, at least_____ receptacle(s) must be installed and in (they) must be protected by a_____device
Front
1, gfci
Back
Any receptacle installed within____ feet of a non-kitchen sink must be GFCI protected asn it must be installed so that it is _________ ________ for monthly testing
Front
6, readily accessible
Back
Floor mounter receptacles are to be installed with-in_____inches of the wall if they are to be considered as the required outlet for that space
Front
18
Back
clock receptacles and receptacles for gas ranges are allowed to be on the small appliance circuits
true or false?
Front
true
Back
Receptacles that serve kitchen counter tops are not allowed to be installed more than____ inches above the counter top and receptacle mountd below the counter top must not be installed where the counter top extends_____" beyond the base cabinet and can be no lower than______" below the top if they are not considered as the requires outlet for that space
Front
20, 6, 12
Back
The receptacle for the refrigerator can be supplied by a 15 or 20 amp circuit rather than using one of the small appliance circuits
true or false
Front
true
Back
In a dwelling , a water heater is considered a continuous load
true or false
Front
true
Back
In North Carolina, by Amendment, a receptacle must be installed at the____of the house and another installed on either the _____ or ______
Front
front, back, side
Back
A wall switch-controlled lighting outlet is required on the interior side of every outdoor entrance
true or false
Front
false
Back
In the laundry area a receptacle must be installed within_____feet of the intended location of the washing machine
Front
6
Back
The small appliance circuits are assigned a load value of______va each when calculating service-entrance requirements
Front
1500
Back
On wall switch-controlled receptacle, installed in a bathroom, would meet the requirements of the NEC for the lighting outlet in that room
true or false
Front
true
Back
In garages, at least____receptacle outlet(s) must be installed and one outlet is required for each____space
Front
1, vehicle
Back
In a crawl space a "pull chain" type fixture is allowed if the control is located where?
Front
a the visual point of entry
Back
Kitchen counter top serving receptacles must be supplied from a minimum of two small appliance circuits
true or false
Front
true
Back
A fixed appliance rating cannot exceed_____% of the circuit rating if it is installed on a circuit with receptacle
Front
50
Back
A small appliance circuits is allowed to supply an outside receptacle if that receptacle is ocated just outside the kitchen, GFCI protected and labeled as such
true or false
Front
true
Back
Food waste disposers and dishwashers are allowed to be connected to the small appliance circuits
true or false
Front
false
Back
A interior stairway with_____ or more risers is required to have a switch located at each level/landing with an_____
Front
6, entryway
Back
Non-sliding fixed glass panels on exterior walls are considered wall space
true or false
On a kitchen counter, a receptacle is required above any counter space_____inches or grater in width and receptacles installed above a counter top must be more than____feet apart