A continuous load is one that is on for more than_____ hours so conductors must be sized at____% of that load

Front

3, 125

Back

In a panelboard, the busses supplying the citcuit breakers are so arranged so that connections directly across from each other are on the same phase and the adjacent connections on each side are on different phases true or false

Front

false

Back

An_____ transfer switch is used to switch a load from its normal primary source to the emergency source without any human interaction and a ______ transfer switch will switch a load but requires a person to operate it

Front

automatic , manual

Back

The NEC requires a minimum of ______ inches of conductor in a box and at least______ inches shall extend past the front of the box

Front

6 , 3

Back

An individual appliance branch circuit shall have a rating less than the appliances "marked rating" True or False

Front

false

Back

Standard light fixture boxes are rated to support fixtures not weighing over_____ pounds

Front

50

Back

Four #4 awg, type THW copper current carrying conductors are installed in a conduit in a boiler connected to these conductors is _____ amps

Front

51

Back

What are the four types of fuel in generators?

Front

propane gas, natural gas, gasoline, diesel

Back

AC systems exceeding____ volts to ground that supplies premise wiring shall be grounded if on 3 phase, 4 wire wye connected circuit

Front

50

Back

A receptacle is required in any habitable room on any wall space_____inches or greater in width and with-in____ feet of a doorway or opening. Wall receptacle are to be placed no more than____feet apart

Front

24, 6, 12

Back

The maximum setting of ground fault protection shall be 1200 amperes and the maximum time delay shall be one second for ground faults equal to or greater than 300 amperes true or false

Front

false

Back

All appliances are required to have a nameplate that indicates.....

Front

identifying name , frequency, volts/amps, watts

Back

Besides the General lighting branch circuits, name the other 20 amps circuits required by the code in a dwelling with a garage. Qty-2: ________, _________, _________, __________

Front

small appliance, laundry branch circuit, bathroom branch circuit, garage

Back

How many 10 stranded conductors are allowed in a 3 X 2 X 2 3/4 device box?

Front

5

Back

The manufactures factory testing of the ground fault equipment is considered adequate true or false

Front

false

Back

In a location where there us heating or air conditioning equipment , a receptacle is to be installed with-in_____feet of the equipment on the same _____

Front

25, level

Back

A box, with clamps, contains 2 # 14/2 NM cables and a receptacle. How much volume must you allow for: clamps______ cu. in, Grounds________, cu. in & receptacle______cu. in

Front

2, 2, 4

Back

What is the minimum cubic-inch volume required for a box that will contain one internal clamp, one switch ( supplied by #14 conductors), and one receptacle ( supplied by # 12 conductors ), two 14/2 NM cables?

Front

30 cu. in

Back

For circuit rated at less than 100 amperes, the terminals for the conductor(s) terminations are rated for ______ degree C conductors

Front

60

Back

A 3200 square foot house, with 600 sq. ft. of additional non-adaptable unfinshed space, requires how many 15 amps lighting branch circuits?

Front

6

Back

How many number 14 conductors allowed in a 4" square box that is 1 1/4 deep?

Front

5

Back

Storage batteries used in emergency systems shall be capable of maintaining the load for____ hours (minimum) and without the voltage dropping below____percent of normal

Front

1 1/2 , 87 1/2

Back

How much volume must you allow in a box for a number 12 conductor?

Front

2.25 cu. in

Back

In bathroom a receptacle must be installed on an______ wall with-in____Ft of the edge of the_____ or in cabinet no more than____inches below the counter top

Front

adjacent, 3, basin , 12

Back

A panelboard's maximum rating is determined by the current carrying capacity of the panel boards internal main______

Front

buss bars

Back

Eight conductors in a conduit must be de-rated to____%

Front

70

Back

If a load is expected to be on for more than three hours, then it is considered to be a (an)________ load

Front

continuous

Back

When the ampacity of a conductor does not correspond to the standard fuse or circuit breaker rating, the code allows you use the next higher rating unless that rating is excess of______ amps

Front

800

Back

Halls greater than_____ feet in length, as measured down the_____ are required to have receptacle

Front

10, center line

Back

A switchboard can be accessible from the front and rear true or false

Front

true

Back

Split-wired duplex receptacles, where only one 1/2 of it is switched, do meet the spacing requirements required by the NEC true or false

Front

true

Back

The NEC requires receptacles to be mounted with the ground up true or false

Front

false

Back

A_____ _______ is the circuit conductors between the final over current protection device and the outlets

Front

branch circuit

Back

If an appliance rating does not exceed 1/8 horsepower or does not exceed 300 volt amps, the branch circuit over current device may serve as the appliances disconnecting means True or False

Front

true

Back

A service is supplied by three number 500 KC MIL conductors per phase, What is the minimum size grounding electrode conductor required?

Front

3/0

Back

Foyers, not part of hall, that have an area greater than_____sq.ft shall have a receptacle installed on any wall space greater than_____feet in width

Front

60, 3

Back

The conductor on the "high-leg" of a 3 phase open delta system must be marked or identified by using the color_____and in panel installed on the _____ phase

Front

orange, B

Back

What table is used to find the value of volt-amperes per square foot for general lighting loads?

Front

220.12

Back

Ground fault protection for equipment shall be provided for solidly grounded wye electrical servies of more than how many volts to ground?

Front

150 volts

Back

In walls constructed of noncombustible materials you are allowed to have a box set back in the wall no more than_____of an inch and gaps around the box cannot exceed_____ of an inch

Front

1/4, 1/8

Back

When sections of electrical equipment are bolted together, non conductive paint, enamel, or similar coatings must be removed to insure good _____ ______

Front

electrical continuity

Back

The NEC allows grounding conductors to be spliced with _________ welding processes

Front

exothermic

Back

Rod and pipe electrodes shall not be less than____feet in length

Front

8

Back

Construction plans for a building are usually called _________ or working drawings and the documents governing all of the material to be used and work to be performed on a construction project are called the ______

Front

blue prints, specifications

Back

Conductors installed in a conduit, that is less than 24 inches long, are not required to be de-rated True or False

Front

true

Back

Show window lighting is required to be calculated at____va per linear foot and in commercial buildings, receptacles outlets are to be calculated at________va each

Front

200, 180

Back

In resistance, the minimum number of lighting branch circuits required is based on ______VA per square ft

Front

3

Back

That portion of the wiring system between the final over current device protecting the circuit and the outlet(s) is called a _________ circuit

Front

branch

Back

The oil in a liquid filled transformer is for cooling and insulation true or false

Front

true

Back

To regard to a commonly used emergency, back-up power source, the initials U P S stand for________ power supply and it's most commonly used source of short term power is ______

Front

uninterruptible, batteries

Back

Section 2

(29 cards)

At least one switched-controlled lighting outlet must be installed in a space containing a water heater true or false

Front

true

Back

On a kitchen island, a receptacle must be installed to serve ant space greater than______" by______"

Front

24 , 12

Back

A lighting fixture must be installed every exterior entrance with ______ ____ access

Front

grade level

Back

On a balcony, a receptacle must be installed no more than____feet above the walking surface

Front

6 1/2

Back

The NEC requires receptacles to be mounted outside of a house in the ______ and _____ of the house, be _____ accessible and not be located higher than____feet above grade level

Front

front, back, readily, 6 1/2

Back

A detached garage that has no wiring is not required to have a receptacle true or false

Front

true

Back

The type NM cable must be secured with-in____" of a box without a clamp, with-in____" of a box with a clamp and every_____feet thereafter

Front

8, 12, 4 1/2

Back

In unfinished basements, at least_____ receptacle(s) must be installed and in (they) must be protected by a_____device

Front

1, gfci

Back

Any receptacle installed within____ feet of a non-kitchen sink must be GFCI protected asn it must be installed so that it is _________ ________ for monthly testing

Front

6, readily accessible

Back

Floor mounter receptacles are to be installed with-in_____inches of the wall if they are to be considered as the required outlet for that space

Front

18

Back

clock receptacles and receptacles for gas ranges are allowed to be on the small appliance circuits true or false?

Front

true

Back

Receptacles that serve kitchen counter tops are not allowed to be installed more than____ inches above the counter top and receptacle mountd below the counter top must not be installed where the counter top extends_____" beyond the base cabinet and can be no lower than______" below the top if they are not considered as the requires outlet for that space

Front

20, 6, 12

Back

The receptacle for the refrigerator can be supplied by a 15 or 20 amp circuit rather than using one of the small appliance circuits true or false

Front

true

Back

In a dwelling , a water heater is considered a continuous load true or false

Front

true

Back

In North Carolina, by Amendment, a receptacle must be installed at the____of the house and another installed on either the _____ or ______

Front

front, back, side

Back

A wall switch-controlled lighting outlet is required on the interior side of every outdoor entrance true or false

Front

false

Back

In the laundry area a receptacle must be installed within_____feet of the intended location of the washing machine

Front

6

Back

The small appliance circuits are assigned a load value of______va each when calculating service-entrance requirements

Front

1500

Back

On wall switch-controlled receptacle, installed in a bathroom, would meet the requirements of the NEC for the lighting outlet in that room true or false

Front

true

Back

In garages, at least____receptacle outlet(s) must be installed and one outlet is required for each____space

Front

1, vehicle

Back

In a crawl space a "pull chain" type fixture is allowed if the control is located where?

Front

a the visual point of entry

Back

Kitchen counter top serving receptacles must be supplied from a minimum of two small appliance circuits true or false

Front

true

Back

A fixed appliance rating cannot exceed_____% of the circuit rating if it is installed on a circuit with receptacle

Front

50

Back

A small appliance circuits is allowed to supply an outside receptacle if that receptacle is ocated just outside the kitchen, GFCI protected and labeled as such true or false

Front

true

Back

Food waste disposers and dishwashers are allowed to be connected to the small appliance circuits true or false

Front

false

Back

A interior stairway with_____ or more risers is required to have a switch located at each level/landing with an_____

Front

6, entryway

Back

Non-sliding fixed glass panels on exterior walls are considered wall space true or false

Front

true

Back

Tpe NMC overall jacket covering shall be_____retardent and_____, __________,_________ resistant

Front

flame, fungus, corrosion, moisture

Back

On a kitchen counter, a receptacle is required above any counter space_____inches or grater in width and receptacles installed above a counter top must be more than____feet apart

Front

12, 4